1234 N Example Dr. #102

Fountain Hills, AZ, 85268

April 21st, 2026

Prepared For:

Terry O'Buyer

inspector
inspector
Riley Tolman
Riley Tolman
#71157
Buyer's Agent
Buyer's Agent
Your Agent
Your agent’s brokerage
Seller's Agent
Seller's Agent
Their Agent
Your Seller Agent Brokerage
16
Repair
13
Evaluate
2
End of life cycle
20
Minor
Information
Scope of Work

Home Safety Considerations for Older Properties

Newer homes are often built with modern safety features that may not be present in older construction. Building codes are updated regularly to reflect improvements in safety and technology. These updates often require new or expanded use of safety devices.

A good example is smoke detectors. They were once considered a luxury, then required as a single device in new homes. Over time, standards changed to require multiple smoke detectors, and now, they must be installed inside and outside each bedroom, as well as in other designated areas of the home.

The following is a list of safety upgrades that buyers may want to consider. These features may not have been required when the home was originally built, and in most cases, sellers are not obligated to install them. However, if the inspector determines that one of these features is a necessary standard for modern homes, it will typically be noted in the inspection report. Some of the items listed below may not apply to this particular property.

General Safety Recommendations

  1. Change the Locks- Re-key or replace all exterior locks and change the tumblers to ensure only authorized individuals have access to the home.
  2. Check Exterior Door Hinges- If exterior doors have exposed hinges, have them evaluated. Hinges that can be accessed from outside may need to be replaced with tamper-resistant versions.
  3. Secure Sliding Glass Doors- Older sliding doors can sometimes be lifted out of their tracks from the outside. Evaluate their condition and consider replacing them if needed for better security.
  4. Schedule a Home Security Survey- Have a licensed security company assess the home before move-in. Install or activate a home security system and reprogram garage door openers and security codes for added safety.
  5. Fireplace Chimney Access- If the chimney is accessible to children, consider adding a protective barrier to prevent burns or injury.
  6. Install a Lock on the Electrical Panel- Locking the main electrical panel helps prevent unauthorized tampering.

Electrical, Plumbing and Fire Safety

  1. Upgrade Two-Prong Outlets- Homes with older two-prong outlets should consider upgrading to grounded three-prong outlets. A licensed electrician can assess and perform this work.
  2. Install GFCI Outlets- Ground Fault Circuit Interrupters (GFCIs) protect against electric shock in areas with moisture. If they’re missing, contact a licensed electrical contractor for installation. These outlets should be installed in: Kitchens, Bathrooms, Garages, Near pools, Outdoor outlets
  3. Add AFCI Protection- Arc Fault Circuit Interrupters (AFCIs) reduce fire risk by detecting electrical arcing. These are required in bedrooms per current codes. Have a licensed electrician evaluate and install them if necessary.
  4. Smoke Detector Placement- Smoke detectors should be installed inside every bedroom and in hallways outside bedrooms. Add detectors if any of these locations are not covered.
  5. Install Vacuum Breakers on Hose Bibs- These prevent contaminated water from entering the home’s water supply through a hose. Install vacuum breakers at all exterior and garage hose bibs if they are not already present.
  6. Install Carbon Monoxide Detectors- If the home uses natural gas or propane appliances, carbon monoxide detectors are essential for safety. CO is an odorless, colorless, and potentially fatal gas.
  7. Check Hot Water Temperature- The water heater should be set no higher than 120°F to prevent scalding. Lower temperatures may be safer if young children are in the home.
  8. Protect the Water Heater in the Garage- In many areas, water heaters located in garages must be protected by a barrier or post to prevent impact from a vehicle, which could cause gas leaks or water damage.
  9. Install an Anti-Tip Device on the Oven- These brackets prevent ovens from tipping forward. If missing, they should be added—especially in homes with children.
  10. Add Safety Sensors to Garage Doors- Modern garage doors are required to have sensors that stop the door if an obstruction is detected. If missing, a professional should install them.
  11. Reprogram Garage Keypad Codes- If your garage door opener has an exterior keypad, change the code to prevent unauthorized access.

Child Safety Considerations

  1. Check Railing Spacing- Stair and balcony railings should not have gaps wider than four inches. If they do, consider modifying them to reduce the risk of a child getting stuck.
  2. Upgrade Pool/Spa Barrier Systems- Ensure proper fencing, self-closing gates, and locking mechanisms are in place to prevent child access. Visit www.aar.com for local requirements.
  3. Replace Old Pool Drain Covers- Older pools with a single, grated drain should have the cover replaced with a modern, safer version by a licensed pool contractor.
  4. Install Childproof Locks and Covers- Use safety covers for outlets and locks for cabinets where hazardous materials may be stored.
  5. Store Hazardous Materials Safely- Keep medications, cleaners, and chemicals like bleach or drain cleaner out of reach of children.

Additional Home Safety Enhancements

  1. Check Fire Sprinkler Heads for Recalls- Many fire sprinkler heads have been recalled in recent years. Visit www.cpsc.gov or www.sprinklerreplacement.com to check your model.
  2. Install a Catch Pan Under the Water Heater- Newer homes often have a drain pan under the water heater to catch leaks and prevent water damage. If not present, consider installing one with a connected drain line.
  3. Add a Catch Pan for Upstairs Washing Machines- If the washing machine is located on the second floor, a pan with a drain line can prevent water damage from leaks.
  4. Check Bedroom Window Size for Egress- Emergency exit standards require bedroom windows to be no more than 44 inches from the floor and have an opening of at least 20 inches wide by 24 inches tall. If bedroom windows do not meet these standards, consider replacement—though this may be costly.
  5. Add Garage Wall Vents- In the Phoenix area, some garages include wall vents to help reduce carbon monoxide buildup. If missing, consider installation.
  6. Evaluate for Scorpions- Scorpions are common in some Phoenix-area neighborhoods. A licensed pest control company can evaluate and advise on prevention steps.
  7. Check for Other Pest Activity- Pest inspections are outside the scope of a typical home inspection. Consider hiring a pest control contractor to check for rodents, insects, birds, and other infestations before closing.
  8. Investigate Environmental Hazards- Hazards such as lead paint, asbestos, and radon are not part of a standard home inspection. Contact the EPA or visit www.epa.gov for more information.
  9. Consult the Consumer Product Safety Commission- For up-to-date product safety information, visit www.cpsc.gov.
Site Details
04.06) Foundation type
Poured Concrete
04.07) Floor construction
Concrete slab
04.08) Wall framing
Wood Stud
04.10) Ceiling structure and type
Drywall
Wood framing
04.11) Roof framing
Trusses
04.14) Moisture in crawl space
N/A
05.15) Wall cladding
Stucco
06.27) Roof(s)
Clay tile
Foam with coating
06.32) Evidence of roof leak
Satisfactory
07.00) Main water shut off valve location
Exterior
North
07.01) Water pressure
81+ see report
Pressure Regulator is installed
07.34) Interior water piping
Copper
07.39) Waste cleanout location
Driveway
Exterior
07.40) Waste/vent piping
ABS
07.43) Water heater
Electric
08.49) Electrical service
Underground
08.53) Electric panel/breaker locations
Exterior on building
Main breaker in main electric panel
08.54) Service amperage/voltage
120/240V
200 Amp
08.55) Branch circuit conductors
Plastic sheathed cable
08.63) Heating type
Central forced
08.64) Heating energy source
Electric
09.68) Heating distribution system
Shared air ducts with cooling
09.70) Fireplace fuel source
Electric simulated
09.70) Fireplace fuel source Stove or Fireplace
Wood
10.72) Cooling type
Central forced air
10.73) Cooling energy source
Electric
10.75 Cooling distribution
Shared ducts with heating
11.85) Evidence of plumbing leak at interior
Yes-see report for details
11.86) Fire egress for bedrooms
Satisfactory
12.87) Insulation type
Townhome/condo, insulation not visible (could not identify)
Approximate Humidity
31%
Approximate Temperature
73° F
Estimated Square Feet
1938
In attendance
Buyer Agent
Inspection Fee
$400
Number of Bathrooms
Three
Number of Bedrooms
Two
Number of Stories
Two
Occupancy
Occupied
Structure orientation
North
Weather Conditions
Mostly clear.
Year Built
1992

1 · Exterior

Information

Our evaluation of the exterior of a property conforms to the Arizona ASHI Standards of Practice and industry standards, and includes the identification of wall cladding, and an evaluation of common components, such as driveways, walkways, fences, gates, handrails, guardrails, yard walls, carports, patio covers, decks, fascia and trim, balconies, doors, windows, lights, and outlets. However, we do not evaluate any detached structures, such as storage sheds and stables, and we do not water test or evaluate subterranean drainage systems or any mechanical or remotely controlled components, such as driveway gates. Also, we do not evaluate any landscape components, such as trees and shrubs (unless there is an adverse impact on the building which would be noted in the report, otherwise satisfactory), fountains, ponds, statuary, pottery, fire pits, patio fans, heat lamps, and ornamental or decorative lighting. Similarly, we do not comment on surface coatings or cosmetic deficiencies and the wear and tear associated with usage or the passage of time that would be readily apparent to the average person.

Unless otherwise noted in the inspection report, the decks, balconies and steps, stoops, porches, areaway, railings, patios, walks, driveway, retaining walls, grading and drainage were satisfactory where visible and readily accessible. (Note that there may be some cosmetic issues that are outside the scope of the inspection.)

The yard (including concrete slabs near the building) should slope away from the building to promote water drainage away from the building to prevent damage. The grading in the Phoenix metro area usually does not meet typical building standards applied in the rest of the United States. The grading should be kept between 4-6 inches away from the wall cladding. If there are areas that do not slope away from the home we recommend improving the drainage around the building. Recommend asking the owners if this has caused problems in the past.

Since the condition of these items may change between the time of our inspection and closing, we recommend that you recheck these items during your final walk through inspection prior to closing.

1.1 · Deck/balcony
Narrative
Deck(s) Issues

Issue: Openings in deck/balconyrailing are relatively wide Explanation: If the openings in a railing are too wide, there is a possibility that a child could slip between the openings in the railings or could get caught between the openings in the railings. (Safety Issue, Repair Recommended)

Repair

2 · Structure*

Overview
Information
Window Issues
Windows
Informational
Issue: Access to some windows was partially obstructed Explanation: If the windows are partially obstructed by furniture, window blinds, drapes, etc., the inspector may not be able to determine if the window is broken, if the dual pane window seal is damaged, if the screens are damaged, if the window opens/closes/locks properly, etc. It is recommended that the windows are rechecked during the final walk-through prior to closing.
2.1 · Eaves Soffits Fascia
Narrative
Eaves soffits fascia Issues

Issue: Peeling paint was noted at the exterior trim (eaves/fascia/soffits) Explanation: Exterior surfaces should be coated with stain or paint to protect them from the elements. Peeling paint indicates that maintenance is required.

Repair
2.2 · Exterior Walls & Ceilings
Narrative
Exterior Walls & Ceilings Issues

Issue: Blisters in paint or stucco noted at the exterior wall(s) or ceiling(s) Explanation: Blisters and/or peeling paint at the exterior walls may be an indication of water intrusion (which can result in damage), or improper installation. Further evaluation is recommended before closing.

Evaluate
2.3 · Exterior Walls & Ceilings
Narrative
Exterior Walls & Ceilings Issues

Issue: Patching noted at exterior Explanation: Patching at the exterior walls or ceilings may indicate current or previous leakage. This appears to be where stucco cracks have been repaired, patching is noticeable. (Evaluation recommended)

Evaluate
2.4 · Exterior Walls & Ceilings
Narrative
Exterior Walls & Ceilings Issues

Issue: Small cracks/gaps/holes/delamination were noted at the exterior wall(s) or ceiling(s) Explanation: It is not unusual for some small exterior cracks to form in buildings. Cracks/holes may result in water leakage and damage. If the exterior of the home is HOA maintained, recommend bringing this to their attention. Normally minor stucco cracks are repaired when the home is painted. (Repair Recommended)

Repair
2.5 · Exterior Walls & Ceilings
Narrative
Exterior Walls & Ceilings Issues

Issue: Small cracks/gaps were noted at/near the at the tops of the parapet walls Explanation: Small cracks may result in water leakage and damage, it is recommended that any cracks/gaps are sealed. Since the tops of the parapet walls are relatively flat, these areas are prone to water intrusion. Further evaluation is also recommended to determine if there is any hidden damage. (Evaluation Recommended)

Evaluate
2.7 · Beams Rafters
Narrative
Beams Rafters Issues

Issue: Repair required at beam/rafter Explanation: A deteriorated, damaged or improperly installed beam may not properly support the structure it is supposed to support. (Repair Recommended)

Repair
2.8 · Columns
Narrative
Columns Issues

Issue: Damage was noted at the support column(s) Explanation: The support columns are the vertical members that hold up a portion of the building, typically a roof. Since the columns are a structural support system for the building, any significant damage should be repaired. If the columns fail, the portion of the building that is supported by the column may settle or collapse. (Repair Recommended)

Repair

3 · Roof/Attic*

Overview
Information
Tile Roof Issues
Concrete or Clay Tile Roof*
Informational
Issue: Low roof pitch or slope was noted at the tile roof Location: Above the patio or porch Explanation: Tiles are a water shedding type of roof, they usually are not installed on a roof that is relatively shallow, because the roof may leak. Note that this roof appears to be part of the original construction, so the design was probably approved by the local building officials. (Monitoring Recommended)
Narrative
Flat roof inspection method* 6.33
MCRR or Foam or Built Up Roof*
Informational
This building is a multi-story condominium type of structure. The roof was not accessible for inspection. If this is a concern for you, further evaluation is recommended before closing. A drone may be used for visual inspection, if conditions permit use.
Flashings and Roof Penetrations Issues
Flashing & Roof Penetrations
Informational
Issue: Skylight(s) installed on building Explanation: Skylights have a reputation for being prone to leakage. Recommend periodically checking the skylights for leakage. (Monitoring Recommended)
Attic Not Applicable
Attic*
Informational
Issue: No attic access was available Location: NA Explanation: Some buildings with "flat" roofs or "cathedral" roofs do not have a typical attic or attic access. In this case the attic cannot be inspected. The type of roof construction, the presence of leaks, the type and amount of attic ventilation, the type and amount of attic insulation, construction in the attic, etc. cannot be determined. If this is a concern for you, further evaluation is recommended before closing.
3.3 · MCRR or Foam or Built Up Roof*
Narrative
Flat Type Roof Issues

Issue: Some elastomeric coating is peeling Location: At numerous locations on the roof Explanation: If the elastomeric covering is peeling, the roof may be more susceptible to leakage and premature deterioration. (Repair Recommended)

Repair
3.5 · Flashing & Roof Penetrations
Narrative
Flashings and Roof Penetrations Issues

Issue: Cracked/broken cover(s) were noted at the skylight(s) Location: On the roof Explanation: Skylights have a reputation for being prone to leakage. Any damage at a skylight should be repaired to ensure that it is weatherproof. (Repair Recommended)

Repair
3.6 · Flashing & Roof Penetrations
Narrative
Flashings and Roof Penetrations Issues

Issue: Gap(s) were noted at the roof flashing Explanation: If there are gaps at the flashings/penetrations the areas with gaps may leak. (Repair Recommended)

Repair

4 · Electrical

Overview
Information
Electric Outlets Issues
Electric outlets
Informational
FYI: Access to some electrical outlets was obstructed Explanation: If the electrical outlets are obstructed by appliances, furniture, stored items, devices plugged into the outlets, etc., the inspector may not be able to determine if the outlets are functional, properly installed, GFCI protected (where required), etc.
4.1 · Main Electric Panel
Narrative
Main Panel Issues

Issue: Indication of overheated wire(s) were noted in the main electric panel Location: In the main electric panel Explanation: Discoloration of the wire and/or melted insulation suggest that the wire has overheated. An overheated wire indicates a potential safety hazard. The cause of the overheating should be identified and corrected. (Safety Issue, Repair Recommended)

Repair
4.2 · Electric outlets
Narrative
Electric Outlets Issues

Issue: GFCI outlet(s) are probably required Explanation: Depending upon the age of the building and other factors, Ground Fault Circuit Interrupter (GFCI) outlets are usually installed in certain locations to reduce the potential for electrical shock. If an area is remodeled, the GFCI usually should be installed where required according to the current standards. If the bathroom was remodeled after 1978/1981, GFCI protection may be required at all outlets in the bathroom. Recommend verifying the correct installation and operation of other outlets that require GFCI protection. (Safety Issue, Repair Recommended)

Repair

5 · Plumbing

Information

We evaluate plumbing systems and their components in accordance with the Arizona ASHI Standards of Practice and industry standards, which include testing for pressure and functional flow. Functional flow is determined by opening each of the fixtures and faucets and observing the volume of water flow. Functional drainage is determined by observing the rate at which the water drains out of the plumbing fixtures. Plumbing systems have common components but they are not uniform. In addition to fixtures, components typically consist of gas pipes, potable water pipes, drain and vent pipes, shut-off valves, which we do not test, pressure regulators, pressure relief valves, and water-heating devices. The best and most dependable water pipes are copper, because they are not subject to the build-up of minerals that bond to the inside of galvanized pipes and gradually reduce their inner diameter and restrict the volume of water. A water softener will remove most of these minerals, but not once they are bonded within the pipes, for which there would be no remedy other than a re-pipe.

The water pressure within pipes is commonly confused with water volume, but whereas high water volume is good high water pressure is not. In fact, whenever the street pressure exceeds eighty pounds per square inch a regulator is recommended, which typically comes factory preset between forty-five and sixty-five pounds per square inch. However, regardless of the pressure, leaks will occur in any system, and particularly in one with older galvanized pipes, and commonly when the regulator fails and high pressure begins to stress the washers and diaphragms within the various components.

Waste pipes are equally varied and are comprised of older ones, such as those made of clay, or others that are made of a material like cardboard coated with tar, and modern plastic ones referred to as ABS. Typically, the condition of these pipes is directly related to their age. ABS pipes, for instance, are virtually impervious to deterioration. However, some ABS pipes are alleged to have manufacturing defects. Regardless, inasmuch as most drainpipes are concealed, we can only infer their condition by observing the draw at drains. Nonetheless, blockages will occur at some point in the life of any system, but blockages in the waste lines, and particularly in a main sewer line, can be costly, and it would be prudent to have the main sewer line video scanned. This would also confirm that the house is connected to the public sewer system, which is important because such systems should be evaluated by a specialist before the end of the inspection period.

Most of the plumbing system in the building is not visible. Therefore the inspector may not be able to determine all of the types of materials used for the plumbing system. If determining the presence of steel, or plastic plumbing systems (such as Polybutylene, PVC, CPVC, PEX, etc.) is important to you, further evaluation by a licensed plumbing contractor is recommended before closing.

During the summer months in the Phoenix, AZ area, the "cold" water may not be very cold. This is especially true if portions of the water distribution system are routed in the attic.

Unless otherwise noted in the inspection report, the interior supply/distribution piping, supports, insulation, fixtures, faucets, waste and vent piping system, water heater equipment and operating controls, flues and vents, fuel distribution system and supports, were satisfactory where visible. (Note that there may be some cosmetic issues that are outside the scope of the inspection.)

Unless otherwise noted in the inspection report, functional flow was noted at the water fixtures and faucets, and functional drainage was noted at the plumbing drains where visible and readily accessible.

Unless otherwise noted in the inspection report, the visible drainage sump(s) and waste ejector pump(s) (if installed) that were visible to the inspector was satisfactory or serviceable.

Unless otherwise noted in the inspection report, no active water supply or drain leaks were observed.

Unless otherwise noted in the inspection report, no cross connections were observed.

Unless otherwise noted in the inspection report, automatic safety controls (e.g. TPR valve, thermocouple, etc.) were noted where required for the water heater(s). Since it is not possible to positively verify the proper operation of these safety devices, it is recommended that they are tested before the end of the inspection period.

Unless otherwise noted in the inspection report, the venting (make up/combustion air) for the gas water heater (if applicable) appears to be typical for this type of system, and may be adequate. Note that the home inspection does not include any engineering analysis for the adequacy of the venting (make up/combustion air) system for the water heater. If this is a concern for you, recommend having this checked before the end of the inspection period.

Since the condition of these items may change between the time of our inspection and closing, we recommend that you recheck these items during your final walk through inspection prior to closing.

5.1 · Main service pipe and pressure
Narrative
Water pressure issues

Issue: High water pressure Explanation: The recommended water pressure at the main water supply is 40 psi to 80 psi. If the water pressure is higher than 80 psi, it can result in problems with plumbing fixtures and damage. If a pressure regulator is installed at this building, the pressure regulator probably is not adjusted properly or is not functioning properly. (Repair Recommended)

Repair
5.2 · Water distribution pipe
Narrative
Water Distribution System Issues

Issue: Corroded plumbing device was noted Explanation: Corrosion is an indication of deterioration of the fixture material. A plumbing device that is corroded may leak. Recommend monitoring for leakage or replace the device. (Repair Recommended)

Repair
5.3 · Water distribution pipe
Narrative
Water Distribution System Issues

Issue: Repair required at water supply system Location: Water heater Explanation: When a pressure regulator or check valve or a back flow preventer has been installed on a home, an expansion tank is required to be installed. This is to be installed at the water heater, to help with thermal expansion. On a tankless heater, if a circulation pump has been installed, then an expansion tank is necessary. No expansion tank has been installed. (SI)

Repair
5.4 · Water heater
Narrative
Water Heater Issues

Issue: Damage noted at water heater housing Explanation: Water heater was noted to have some mechanical damage. This may have resulted in damage to the inner tank. This may result in premature failure of the water heater. This may also be primarily cosmetic damage.

Evaluate

6 · Parking/garage

Information

Since the condition of the equipment may change between the time of our inspection and closing, we recommend that you recheck these items during your final walk through inspection prior to closing.

Unless otherwise noted in the inspection report, the fire separation walls and fire separation door(s) appear to be properly installed and functional where visible and readily accessible. Note that the home inspector cannot always determine the thickness, and therefore the effectiveness, of the fire separation walls. If the door between the house and garage does not have a label on it indicating that it is approved for this purpose (most of them do not have this label), the home inspector cannot positively verify that it is a fire rated door.

If there is an exterior keypad installed for the overhead garage door, recommend having it reprogrammed when moving in, to prevent unauthorized access. Unless otherwise noted in the report The overhead garage door(s) and opener(s) were satisfactory and did reverse properly when they were tested by operating the normal controls (usually the wall mounted switch) and noting if the door stops and reverses when the door path is blocked by a 2X4 placed on the floor below the garage door. For safety reasons, it is recommended that this is periodically rechecked.

6.1 · Vehicle Parking
Narrative
Vehicle Parking Issues

Issue: No vents noted in exterior garage wall Explanation: Vents are installed in the exterior walls of garages to reduce the opportunity for exhaust fumes to enter the house in the event that a car is left running or automatically starts in the garage. If the home is also equipped with a gas water heater in the garage, should the gas begin to leak, it becomes trapped in the garage and may leak into the home. (SI)(Repair Recommended)

Repair

7 · HVAC

Overview
Information
Satisfactory cooling system
Cooling System
Informational
FYI: The temperature split was within the normal range Explanation: The difference between the air temperature entering the air conditioner cooling coil and the air temperature leaving the air conditioner cooling coil (the temperature split) typically should be 18 to 22 degrees. The temperature split for the AC unit was within this range.
NarrativeNarrativeNarrativeNarrative
7.1 · HVAC System
Check HVAC system for servicing

Issue: Recommend verifying that HVAC system(s) are serviced Explanation: It is recommended that heating/cooling/air distribution systems are serviced each year to ensure that they are functioning properly and are safe. Recommend asking the owners for documentation indicating that it has been serviced within the last year. If documentation is not available, recommend having the unit serviced before the end of the inspection period. (Evaluation Recommended)

Evaluate
7.2 · Air Distribution System
Narrative
Air Distribution System Issues

Issue: Stains and/or damage were noted at/under the air handler Explanation: The water stains/damage may indicate previous leakage. If the possibility of hidden damage or allergens is a concern for you, further evaluation is recommended before the end of the inspection period. (Evaluation Recommended)

Evaluate

8 · Interior

Overview
Information
Second Floor Construction Type
Interior Flooring
Informational
The second floor construction type could not be determined because the second floor support structure was not visible. The floor system is probably plywood or OSB over wood floor joists, trusses or engineered floor beams.
8.2 · Interior Walls-Ceilings
Narrative
Interior Walls and Ceilings Issues

Issue: Water stains or damage were noted at the interior Explanation: Water stains and or damage usually indicate previous water leakage. If the possibility of hidden damage is a concern for you, further evaluation is recommended before the end of the inspection period. (Evaluation Recommended)

Evaluate

9 · Bathroom

Information

Our evaluation of bathrooms conforms to the Arizona ASHI Standards of Practice and industry standards. We do not comment on cosmetic deficiencies, and we do not evaluate window treatments, steam showers and saunas, nor do we leak-test shower pans, or test overflow drains.

If a toilet is installed on a tile floor, it is recommended that grout is installed between the base of the toilet and the floor. This can help to ensure that the toilet will not rock on the uneven tile surface and become loose, which can result in leakage. Caulk is often used between the toilet and tile floor. While this may be acceptable, in our experience, when grout is used between the base of the toilet and the floor, the toilet is much less likely to move.

Any water stains may indicate current or previous water leakage. Mold may be found in areas with current or past high moisture levels and water leakage. Note that determining the presence of mold is outside the scope of this inspection. If any signs of stains or water damage are noted anywhere in the inspection report, further evaluation is recommended before closing by a specialist to determine if mold exists. If you are concerned about the presence of mold, it is recommended that you have a specialist perform a complete mold assessment, including testing the indoor air.

Unless otherwise noted in the inspection report, the bathroom(s) appear to have a source of ventilation. If the bathroom is equipped with a fan, it was tested using normal operating controls and was satisfactory unless noted in the report otherwise.

Unless otherwise noted in the inspection report, the whirlpool or jetted tub (if installed) was satisfactory or serviceable and was on a GFCI device.

Since the condition of the bathrooms may change between the time of our inspection and closing, we recommend that you recheck these items during your final walk through inspection prior to closing.

9.1 · Sinks
Narrative
Bathroom sinks

Issue: Evidence of leakage was noted below the bathroom sink Explanation: Water and or stains noted under the sink. Water leakage can result in damage. (Repair Recommended)

Repair
9.2 · Tub & Shower
Narrative
Bathtub & Shower

Issue: Gaps/voids noted in the bathtub/shower grout/caulking (cracks/gaps noted in tile or enclosure) Explanation: Any gaps in the tile or other surfaces near the bathtub/shower that could get wet should be sealed to prevent moisture intrusion and possible damage. If you are concerned about the possibility of hidden damage, further evaluation is recommended before the end of the inspection period. (Evaluation Recommended, Repair Recommended)

Evaluate

10 · Kitchen

Information

Please note that the kitchen appliances were tested according to the scope of the inspection as detailed in the Arizona ASHI Standards of Practice. We do not check thermostats or timers, we do not comment on cosmetic deficiencies. We cannot comment on efficiency of the appliance. The appliance may fail at any time, therefore these are not warrantied under the Alta Vista 100-day inspection guarantee. It is recommended that the appliances are tested prior to closing to ensure these are still operational. Common appliances that are tested (when installed) are ovens, ranges, surface cooking appliances, microwave ovens, dish-washing machines and food waste grinders, by using normal operating controls (to activate the primary functions). Unless otherwise noted in the report the appliances were satisfactory and functional. Any stored items in the appliance will prevent operation.

Any water stains may indicate current or previous water leakage. Mold may be found in areas with current or past high moisture levels and water leakage. Note that determining the presence of mold is outside the scope of this inspection. If any signs of stains or water damage are noted anywhere in the inspection report, further evaluation is recommended before closing by a specialist to determine if mold exists. If you are concerned about the presence of mold, it is recommended that you have a specialist perform a complete mold assessment, including testing the indoor air.

Unless otherwise noted in the inspection report, the kitchen appears to have a source of ventilation for the stove.

Since the condition of the kitchen appliances, sinks, cabinets, etc. may change between the time of our inspection and closing, it is highly recommended that they are rechecked during your final walk through inspection before closing.

10.1 · Kitchen Counter Top & Cabinets
Narrative
Kitchen Counter Tops and Cabinets Issues

Issue: Water stains or damage were noted at the kitchen cabinet(s) Location: Under the kitchen sink Explanation: Water stains and/or damage usually indicate previous water leakage. If the possibility of hidden damage or allergens is a concern for you, further evaluation is recommended before the end of the inspection period. (Evaluation Recommended)

Evaluate
10.2 · Range Hood
Narrative
Range Hood Issues

Issue: Air leak at range hood Explanation: A downward draft was not below the exhaust hood. This may result in the gas flame extinguishing. Should this occur, unburned gas will enter the home. (SI)

Repair

11 · Laundry

Overview
Information
Misc Laundry Room Issues
Misc. laundry room issues
Informational
Issue: No clothes washer/dryer installed Explanation: If no clothes washer or dryer is installed, the water supply, drain, venting and gas/electric supply cannot be tested at time of inspection. Recommend having these checked before the end of the inspection period. There are some additional tests that could be performed in the laundry area, which are outside the scope of the Home Inspection. If you would like to have Alta Vista perform these additional tests, please call the Inspector for a quote.

12 · Fireplace/chimney

Overview
Information
Fireplace Issues
Fireplace(s)
Informational
Issue: Cosmetic imperfections were noted at the fireplace Explanation: Identifying specific cosmetic imperfections is outside the scope of the home inspection. If cosmetic imperfections are noted at a new home, these should be pointed out to the builder for correction.
Chimney Issues
Chimney(s)
Informational
Issue: Fireplace chimneys not fully visible (inspection limited) Location: This comment applies to all fireplace chimneys Explanation: Due to the height of the house or the location of the chimney it will not be fully visible at time of inspection. In this case, the inspection is limited to what can be seen. If this is a concern for you, further evaluation is recommended before the end of the inspection period.

13 · Misc.

Overview
Information
Miscellaneous Issues
Miscellaneous Comments
Informational
Issue: The SPDS was not available Explanation: The Seller's Property Disclosure Statement (SPDS) was not provided to the Home Inspector at the time of the inspection, so the Inspector could not review it. This is not a requirement. Some individuals will provide the inspector the SPDS to review prior to or at the inspection. The inspector is not required to review the SPDS, but will do so as a courtesy to the buyers. This document should be carefully reviewed by Buyer and agent, before closing, since it may disclose additional items that need to be corrected or evaluated.
Miscellaneous Issues
Miscellaneous Comments
Informational
Issue: Stored items noted (inspection limited) Explanation: Kitchen cabinets, bathroom cabinets, hall cabinets, garages, garage cabinets, closets, etc. are often used as storage areas, especially for buildings built on concrete slabs that do not have basements. Personal items such as furniture, rugs, window treatments, etc. can also restrict access or limit visibility. Areas that are not visible cannot be inspected for evidence of leakage, stains, damage, etc. It is recommended that the buyer pay particular attention to these areas during the final walk through before closing, or have these areas reinspected after the stored personal items have been removed.
Vacuum Cleaner - built in
Miscellaneous Comments
Informational
FYI: House is pre-plumbed for central vacuum, but installation not completed Explanation: The building appears to be pre-plumbed for a central vacuum system, but the installation does not appear to be completed.
13.1 · Miscellaneous Comments
Narrative
Insects-termites-pets-pests

Issue: Possible evidence of pests was noted (what appears to be droppings were noted) Explanation: Evidence of pests was noted in or near the building, such as rodent, insect etc. Recommend asking the owners if there have been any problems with rodents, in the past. Recommended having a pest control contractor check the building and provide recommendations for pest control. (Safety Issue)

Evaluate
13.2 · Miscellaneous Comments
Insects-termites-pets-pests

Issue: Mud tubes, or remnants of mud tubes, or evidence of termite activity, are suspected Location: See termite inspection report for details Explanation: Some types of wood destroying organisms leave tell tale mud tubes or damage that indicate they have been in or on the building at some time in the past. If mud tubes/damage are noted, it is recommended that the building is checked by a pest control contractor with expertise in termite inspections. Note that the home inspector is not licensed or qualified to determine the presence or absence of wood destroying organisms, and this determination is outside the scope of the home inspection. Also, recommend evaluation to determine if there is any termite damage and the extent of any damage. (Evaluation Recommended)

Evaluate
13.5 · Miscellaneous Comments
Miscellaneous Issues

Issue: Recommend verifying and copying building permits Location: For all additions and modifications requiring permits Explanation: Recommend asking the sellers if permits were obtained (when required) and if the modifications have been approved by the local building authority. If no permits are available, further evaluation of the modifications is recommended to ensure that they comply with local building codes and installation instructions. Also, recommend obtaining copies of warranties for any recent work. (Evaluation Recommended)

Evaluate

14 · Est. Age

Overview
Information
AC condenser
Estimated Age of Major Components
Informational
The typical useful life span for an air conditioner condenser system in this area is about 15 to 20 years. The AC condenser system is estimated to be 1 to 5 years old.
NarrativeNarrative
AC condenser
Estimated Age of Major Components
Informational
The typical useful life span for an air conditioner condenser system in this area is about 15 to 20 years. The AC condenser systems are estimated to be 10 to 15 years old. Recommend budgeting for replacement and recommend verifying that these items are covered by your Home Warranty.
Narrative
Air handler-Furnace
Estimated Age of Major Components
Informational
The typical useful life span for an air handler/furnace/cooling coil system in this area is about 15 to 20 years. The air handler/furnace/cooling coil system is estimated to be 10 to 15 years old. Recommend budgeting for replacement and recommend verifying that this item is covered by your Home Warranty.
Narrative
Exterior paint
Estimated Age of Major Components
Informational
The exterior paint/stain in this area has an average life expectancy of about 5 years. Some of the exterior paint/stain is estimated to be over 5 years old. Recommend budgeting for repainting.
Dual pane windows
Estimated Age of Major Components
Informational
The typical useful life span for dual pane window seals (before internal condensation is likely) is about 5 to 10 years. Note that the typical life span will vary, depending upon the exposure of the window to sunlight and other factors. Most of the dual pane windows are estimated to be 1 to 5 years old.
Roofing paper (under roof tiles)
Estimated Age of Major Components
Informational
The roofing paper (mineral coated roll roofing) under the tile roof has an average life expectancy in this area of about 20 - 25 years. Recommend asking the current owner when the mineral coated roll roofing (roofing paper) was last replaced.
Kitchen appliances
Estimated Age of Major Components
Informational
The typical useful life span for kitchen appliances is about 5 to 10 years. Most of the kitchen appliances are estimated to be over 5 years old. Recommend rechecking these during your final walk through before closing.
Water heater
Estimated Age of Major Components
Informational
The typical useful life span for a water heater in this area is about 5 to 10 years. The water heaters are estimated to be 1 to 5 years old.
Narrative
Water shut off valves - plumbing fixtures
Estimated Age of Major Components
Informational
The typical useful life span for plumbing fixtures (toilets, sink faucets, bathtub/shower faucets, water shut off valves, etc.) in this area is about 5 to 10 years. Note that this can vary widely, depending on the chemistry of the water. Since this building is over 5 years old, recommend budgeting for replacement of the plumbing fixtures.
14.6 · Estimated Age of Major Components
Elastomeric coated roof

The elastomeric coating on the roof in this area has an average life expectancy of about 5 years. The elastomeric coating is estimated to be over 5 years old. Further evaluation of the roof is recommended before the end of the inspection period. Also, recommend budgeting for maintenance, such as re-coating the roof.

End of life cycle
14.9 · Estimated Age of Major Components
Smoke detectors

The typical useful life span for smoke detectors is about 5 to 10 years. Most of the smoke detectors are estimated to be over 10 years old (based on the age of the building). Recommend asking the current owners if they have ever been replaced. If not, recommend evaluating them for replacement. Also recommend routinely testing the smoke detectors, as recommended by the manufacturer.

End of life cycle

15 · Misc. Minor

Information

The following items require repair/servicing/evaluation. Issues with possible safety implications are marked (SI). Correcting each of the items listed in this section of the inspection report is expected to cost less than 1/2 of 1 percent of the value of the real property. We recommend that the Buyer verify the cost of having these items corrected by obtaining bids before the end of the inspection period.

15.1 · Minor Repair-Service-Evaluation Items
Miscellaneous Repair-Service-Evaluation Items

Issue: Miscellaneous Repair/Service/Evaluation Items Explanation: The following items require repair/servicing/evaluation. Correcting each of these items is expected to cost less than 1/2 of 1 percent of the value of the real property. Issues with possible safety implications are marked (SI). Please contact the Home Inspector if you have questions about any of these issues.

Minor
15.2 · Minor Repair-Service-Evaluation Items
Narrative
Ceiling Fans

Some ceiling fans are out of balance. (SI)

Minor
15.3 · Minor Repair-Service-Evaluation Items
Narrative
Electrical

Some circuit breakers (in the electric panel(s)) are not labeled (or labels are not legible or not clear).

Minor
15.4 · Minor Repair-Service-Evaluation Items
Narrative
Electrical

Non OEM circuit breakers noted in main electric panel. (SI) (Some circuit breakers were not made by the same company that made the electric panel.)

Minor
15.5 · Minor Repair-Service-Evaluation Items
Narrative
Electrical

Loose junction box noted. (SI)

Minor
15.6 · Minor Repair-Service-Evaluation Items
Narrative
Electrical

Loose electric outlet noted. (SI)

Minor
15.7 · Minor Repair-Service-Evaluation Items
Narrative
Electrical

Light fixture not installed at exterior door(s). Lights should be installed at exterior door to illuminate the area, to avoid tripping hazards.

Minor
15.8 · Minor Repair-Service-Evaluation Items
Narrative
Electrical

Half hot outlet not installed upside down. Half hot outlets are typically identified by being installed upside down. One half of the outlet is controlled by a switch for lamp control.

Minor
15.9 · Minor Repair-Service-Evaluation Items
Narrative
HVAC

Exposed fiberglass insulation noted in the air supply plenum below the air handler. (SI)

Minor
15.10 · Minor Repair-Service-Evaluation Items
Narrative
HVAC

The vent do the AC condensate drain was noted to be too low. Should the drain clog and back up, it can overflow through the vent and cause damage below.

Minor
15.11 · Minor Repair-Service-Evaluation Items
Narrative
Parking-Garage

Some gaps noted at trim by overhead garage door.

Minor
15.12 · Minor Repair-Service-Evaluation Items
Parking-Garage

There is a key pad installed for the overhead garage door opener. Recommend resetting the code for the garage door opener, after closing.

Minor
15.13 · Minor Repair-Service-Evaluation Items
Narrative
Parking-Garage

The sink in the garage is not secured in place. Recommend securing the sink (e.g. attach to wall) to reduce the opportunity for leakage.

Minor
15.14 · Minor Repair-Service-Evaluation Items
Narrative
Parking-Garage

The overhead garage door did not properly reverse when closing on a 2X4. (SI)

Minor
15.15 · Minor Repair-Service-Evaluation Items
Narrative
Parking-Garage

Some holes noted at ceiling in the garage. (Fire safety issue) (SI)

Minor
15.16 · Minor Repair-Service-Evaluation Items
Narrative
Pests

Wasp nest noted. (SI)

Minor
15.17 · Minor Repair-Service-Evaluation Items
Narrative
Structure

Some damaged exterior trim noted.

Minor
15.18 · Minor Repair-Service-Evaluation Items
Narrative
Structure

Missing nails at hanger

Minor
15.19 · Minor Repair-Service-Evaluation Items
Narrative
Water Heater

Recommend installing/ extending pipe, to the exterior, on secondary pan for water heater to prevent damage.

Minor
15.20 · Minor Repair-Service-Evaluation Items
Narrative
Water Softener

No overflow tube installed on water softener brine tank. If the brine tank overflows, it can result in damage.

Minor

16 · Scope

Overview
Information
Sewer scope
Items Outside the Scope of Inspection
Informational
Issue: Optional Sewer Scope Inspection Declined Explanation: Please be advised that the optional sewer scope inspection service was declined at the time of scheduling. According to the Arizona Standards of Practice and the terms outlined in the Inspection Agreement, the inspection of underground sewer lines and drainage systems is beyond the scope of a standard home inspection. Therefore, these components are not included in the general inspection. Alta Vista offers sewer scope inspections as an optional service for an additional fee. This service involves inserting a specialized camera into the main sewer line to assess its condition. Issues such as root intrusion, pipe damage, blockages, or deterioration may not be visible during a standard inspection but can result in costly repairs if left undetected. Although this service was not selected, we recommend a sewer scope inspection to evaluate the condition of the property’s main sewer line, particularly for older homes or homes with large trees on the property.
Radon Gas
Items Outside the Scope of Inspection
Informational
Issue: Optional Radon Screening Service Declined Explanation: Please be advised that the optional radon screening service was declined at the time of scheduling. Per the Arizona Standards of Practice and the Inspection Agreement, certain systems, components, and environmental conditions fall outside the scope of a standard home inspection. As such, radon testing is not included in the base inspection. Alta Vista offers radon screening as an optional service for an additional fee. Radon is a naturally occurring radioactive gas that emanates from the ground. It is odorless, tasteless, and cannot be detected without specialized equipment. Prolonged exposure to elevated radon levels has been linked to an increased risk of lung cancer. Although this service was not selected, we recommend radon testing to determine whether mitigation measures may be necessary for the property.
Thermal Imaging
Items Outside the Scope of Inspection
Informational
Issue: Optional equipment inspection was declined (Thermal imaging) Explanation: Inspecting some items/systems/equipment is outside the scope of the inspection, as outlined by the Arizona Standards of Practice and the Inspection Contract. Therefore, they are not included in the normal inspection. Alta Vista offers an optional service, at additional cost, to inspect the interior of the home with a thermal imaging camera, this helps identify primarily missing insulation, it may also identify active plumbing leaks, active roof leaks so long as the surface or areas are still wet and overheating electrical equipment. This optional service was declined when the inspection was ordered. We recommend that you have this performed, before the end of the inspection period. Since these items were not inspected, Alta Vista assumes no liability for these items, and they are not covered by our 100-Day Guarantee.
Outdoor Living
Items Outside the Scope of Inspection
Informational
Issue: Optional equipment inspection was declined (Outdoor Living Package) Explanation: Inspecting some items/systems/equipment is outside the scope of the inspection, as outlined by the Arizona Standards of Practice and the Inspection Contract. Therefore they are not included in the normal inspection. Alta Vista offers an optional service, at additional cost, to inspect the irrigation (exterior plant watering) system, water features, BBQ grill, landscape lights, exterior fireplace/fire pits/fire pots, mist system, motorized awnings, etc. This optional service was declined when the inspection was ordered. We recommend that you have the seller demonstrate the operation of these systems, and/or that they be inspected before the end of the inspection period. Since these items were not inspected, Alta Vista assumes no liability for these items, and they are not covered by our 100-Day Guarantee.
Cursory check performed
Items Outside the Scope of Inspection
Informational
FYI: Cursory check may have been performed on some of the items listed below Cursory check performed on following items: Kitchen appliances, irrigation (exterior plant watering) system, ceiling fan(s), washer/dryer, water circulation loop, water softener, reverse osmosis filter Explanation: Inspecting some items/systems/equipment is outside the scope of the inspection, as outlined by the Arizona Standards of Practice and the Inspection Contract. As a courtesy to the Buyer/Homeowner, the Inspector will perform a cursory check of certain systems, when it is practical to do so, at no charge to the customer. Since this service is free, Alta Vista assumes no liability for these systems, and they are not covered by our 100-Day Guarantee. If you would like to have Alta Vista perform a thorough inspection of these systems (which would then be covered by our 100-Day Guarantee), please call the Inspector for a quote.
16.1 · Items Outside the Scope of Inspection
Termite/WDO

Issue: Optional Termite/Wood-Destroying Organism (WDO) Inspection Completed Explanation: A Termite/Wood-Destroying Organism (WDO) inspection was selected and completed as part of this home inspection through a licensed pest control company. This optional service, organized through Alta Vista for an additional fee, is specifically designed to identify signs of wood destroying organisms, prior treatments, or damage caused by wood-destroying organisms such as termites. Please note that under the Arizona Standards of Practice and the terms of the Inspection Agreement, WDO inspections fall outside the scope of a standard home inspection. Accordingly, this evaluation was performed independently by a licensed pest control provider. Alta Vista assumes no liability for the findings, results, or conclusions of the WDO inspection. The company will provide their findings directly to the consumer and or their authorized representatives, we recommend thorough review of their findings/report. For any questions, concerns, or follow-up related to this inspection, please contact the pest control company that conducted the service directly.

Evaluate